A foot candle is one lumen landing on one square foot. Everything about whether a space feels right comes back to this number, how evenly it is spread, and where somebody measured it. Here are working targets for the spaces you are most likely to be quoting.
Warehouse and industrial
| Space | Target | Measured at |
|---|---|---|
| Bulk storage, infrequent access | 5 to 10 fc | Floor |
| Active storage, forklift traffic | 10 to 20 fc | Floor |
| Rack aisles, order picking | 20 to 30 fc | Vertical, in the aisle at rack face |
| General assembly | 30 to 50 fc | 30 inches above floor |
| Detailed assembly, machining | 50 to 75 fc | At the work |
| Inspection, fine detail | 75 to 100 fc | At the work, usually task lighting |
| Loading dock | 20 to 30 fc | Floor, plus dock lights at doors |
| Mechanical and electrical rooms | 20 to 30 fc | Floor |
Fixtures: high bays above about fifteen feet, strip lights below that.
Office and commercial
| Space | Target | Measured at |
|---|---|---|
| Open plan office | 30 to 40 fc | Desk height, 30 inches |
| Private office | 30 to 50 fc | Desk height |
| Conference room | 30 to 40 fc | Table height, dimming worth having |
| Corridor, lobby | 10 to 20 fc | Floor |
| Break room | 20 to 30 fc | Table height |
| Restroom | 10 to 20 fc | Floor, more at the mirror |
| Stairwell | 10 fc minimum | Tread, and check egress requirements |
| Server or IT room | 30 to 50 fc | Vertical at the rack face |
Fixtures: panels and troffers in drop ceiling, down lights in hard ceiling, wraparounds in utility space.
Retail
| Space | Target | Notes |
|---|---|---|
| General sales floor | 30 to 50 fc | Higher for value retail, lower for premium |
| Feature and display | 2 to 5x the general level | Contrast is what draws the eye, not raw level |
| Grocery, big box | 50 to 75 fc | Uniform and bright is the whole aesthetic |
| Fitting room | 30 to 50 fc | Colour rendering matters more than level |
| Checkout | 50 fc | Vertical light on faces, not just down |
| Stockroom | 20 to 30 fc | Floor |
Schools and healthcare
| Space | Target | Notes |
|---|---|---|
| Classroom | 30 to 50 fc | Desk height, low glare, dimming for screens |
| Gymnasium | 30 to 50 fc | Higher for competition play, uniformity critical |
| Library, reading | 30 to 50 fc | Vertical light on the stacks too |
| Cafeteria | 20 to 30 fc | Table height |
| Patient room | 10 to 30 fc | General, with separate exam lighting |
| Exam room | 50 to 100 fc | At the table, high colour rendering |
| Nurse station | 50 fc | Work surface |
| Corridor, daytime | 10 to 20 fc | Often reduced at night |
Parking and exterior
| Space | Target | Notes |
|---|---|---|
| Open parking lot, basic | 0.5 to 1 fc average | Minimum matters more than average here |
| Open parking lot, enhanced security | 1 to 3 fc average | Retail and hospitality typically |
| Parking garage interior | 5 fc | Floor, and the fixtures run 24 hours |
| Garage ramps and entries | 10 to 20 fc daytime | Eyes need a transition zone from daylight |
| Building entrance | 5 to 10 fc | Vertical light on faces for cameras |
| Walkway, path | 0.5 to 2 fc | Uniformity beats brightness |
| Loading and service yard | 5 to 10 fc | Floor |
| Fuel canopy | 20 to 30 fc | Under the canopy, and it is a dark sky issue |
Fixtures: area lights on poles, wall packs on buildings, canopy under cover, bollards on paths.
The number nobody asks about: uniformity
Average foot candles will not tell you whether a space looks good. Uniformity will.
| Space | Target ratio |
|---|---|
| Office, classroom, retail | 3:1 or better |
| Warehouse general | 4:1 or better |
| Parking lot | 4:1, and no worse than 15:1 max to min |
| Sports and gym | 2:1, which is why these layouts get dense |
A parking lot at 1.5 foot candles average sounds fine until you find out it is 6 foot candles under each pole and 0.2 between them. The average is right and the lot is unusable, because the human eye adapts to the bright spot and then cannot see into the dark one. This is the single most common reason a client says the new lighting looks worse than what came out.
Interior spaces are more forgiving than exterior. Walls and ceilings bounce light around and fill in the gaps. Outside there is nothing to bounce off, which is why pole spacing and distribution type matter so much more than fixture wattage.
How to measure so the number means something
- Measure at the work plane, not the floor. Thirty inches for desks and benches. The floor is only the work plane in a warehouse.
- Take a grid, not a spot. Walk a pattern and record several readings. One reading directly under a fixture proves nothing.
- Kill the daylight. Measure at night or with blinds closed, or you are measuring the sun.
- Let LED settle. Give fixtures a few minutes to reach steady output before reading.
- Hold the meter flat and stand out of the way. Your own shadow will move a reading more than you expect.
- Record the existing levels before you demo anything. It settles arguments later, and it is what the utility asks for if a rebate is involved.
Turning a target into a fixture count
Once you have a target, the lumen method gets you to a fixture count in about two minutes. That method, with a worked example, is in how many high bays do you need for a warehouse. It works the same way for panels, strips and troffers, only the fixture lumens change.
One shortcut worth knowing: most of what we carry is wattage selectable, so you can lock the layout in first and set the output afterward once you have walked the space with a meter. That is a lot easier than reordering.
Tell us the space and we will tell you the fixture
Square footage, ceiling height and what happens in the room. We will come back with the fixture, the count and a price you can put in the bid.